- Totally self-contained, maintenance-free operation.
- 39,000 Btu cooling capacity to handle any hot spot.
- Less than half the cost of central air conditioning…no costly installation is necessary.
- Handles temperatures up to 115°F. provides cooling in the hottest environments.
- Rugged design… proven durability since 1982.
CLASSIC 40
CUSTOMIZABLE AND ADAPTABLE
For larger applications, the United Mobile Heating and Cooling Classic 40 portable industrial cooling unit can create flexible, mobile or temporary cooling in factories and warehouses. Using multiple T-section drops, you can customize an adaptable portable air conditioner solution for your manufacturing or assembly lines. Add an optional wagon kit or casters to the units and you can move the cool air as your assembly or process line changes.
By cooling only the area that needs it, the Classic 40 industrial air conditioning unit saves you money while protecting people and equipment and speeding up processes.
SPECIFICATIONS
Electronic Features
|
Control Panel
|
Digital
|
---|---|---|
Thermostat Control | Electronic | |
Cooling Capacity
|
Rating Conditions: 95°F at 60% RH
|
39,000 Btu/h
|
Electrical
Characteristics
|
Voltage Requirement
|
3 Phase, 220V
|
Total Power Consumption | 4.2 kW | |
Current Consumption | 14 amps | |
Recommended Fuse Size | 25 amps | |
NEMA Plug Configuration | L15-30 | |
Min. Max. Voltage | 198 – 240 | |
Fans
|
Motor Output
|
0.75 kW Evap.
0.40 kW Cond.
|
Evaporator
|
Fan Type
|
Centrifugal
|
Max.Air Flow high/low | 1060 CFM | |
Max. External Static Pressure | 1.73 IWG | |
Condenser
|
Fan Type
|
Propeller
|
Max. Air Flow high/low | 2650 CFM | |
Max. External Static Pressure | 0.05 IWG | |
Compressor
|
Type
|
Hermetic Scroll
|
Output | 2.3 kW | |
Refrigerant
|
R-410A
|
3.9 lb
|
Dimensions
|
W x D x H
|
26 x 44 x 38 in
|
Net Weight/
Shipping Weight
|
344/396 lb
|
|
Power Cord
|
Gauge
|
12 AWG (4-core)
|
Length | 6 ft | |
Condensate
Tank Capacity
|
2 @ 5 gal (Optional)
|
|
Operating Conditions
|
Min. Max. (@ 50% RH)
|
75° – 115°F
|
Max. Duct
Length
|
Per Cold Duct Hose
|
Varies
|
Hot Duct Hose | 40 ft | |
Max.
Sound Level
|
With Condenser – Duct high/low
|
N/A
|
Without Condenser – Duct high/low | 72 dB(A) |