OFFICE PRO 60

  • Operates on 220v power.
  • Provides 60,000 Btu/hr of cool air… maximum spot cooling to just the room that needs it.
  • No costly installation necessary … simply roll it in, plug it in, turn it on.
  • Condensation pump included … pumps water to remote drain for uninterrupted operation.
  • 24/7 programmable operating modes.

COMPUTER COOLING
OFFICE & SERVER ROOM AIR CONDITIONER UNITS

Providing up to 60,000 Btu/hr of computer cooling capacity (more than twice the cooling power of the Office Pro 24), the Office Pro 60 portable air conditioner is specifically designed for cooling large office spaces and computer rooms that house heat-generating electronics. As an ideal server room air conditioner, it prevents computer networks, communications, and office equipment from shutting down when temperatures rise.

Avoid crippling daily operations by bringing portable A/C to just the area or room that needs it. Protect critical data from being lost with an Office Pro 60. This powerful computer room air conditioner saves you money while protecting your company’s investment in equipment, employees and customers. Self-contained and portable, the Office Pro 60 requires no costly installation – simply roll it in, plug it in and turn it on.

** Exhaust duct required in most cases.

SPECIFICATIONS

Electronic Features
Control Panel
Programmable
Thermostat Control Electronic
Cooling Capacity
Rating Conditions: 95F at 60% RH
60,000 Btu/h
Electrical Characteristics
Voltage Requirement
1 Phase, 208/230V
Total Power Consumption 6.6 kW
Current Consumption 29 amps
Recommended Fuse Size 50 amps
NEMA Plug Configuration 6 – 50
Min. Max. Voltage 198 – 250
Fans
Motor Output
0.5/0.33 kW Evap.
1.2/0.93 kW Cond.
Evaporator
Fan Type
Centrifugal
Max Air Flow high/low 1940/1770 CFM
Max External Static Pressure 0.9 IWG
Condenser
Fan Type
Centrifugal
Max Air Flow high/low 2830/2650 CFM
Max External Static Pressure 0.85 IWG
Compressor
Type
Hermetic Rotary
Output 3.9 kW
Refrigerant
R-410A
3.97 lb
Dimensions
W x D x H
30 x 52 x 64 in
Net Weight/Shipping Weight
623/753 lb
Power Cord
Gauge
6 AWG (3 – core)
Length 6 ft
Condensate Tank Capacity
Auto Pump Included
Operating Conditions
Min. Max. (@ 50% RH)
65° – 105°F
Max. Duct Length
Per Cold Duct Hose
40 ft
Hot Duct Hose 100 ft
Max. Sound Level
With Condenser – Duct high/low
69/67 dB(A)
Without Condenser – Duct high/low 71/69 dB(A)

Note: All specifications subject to change without notice.